Long Description:
The ESB63..N installation contactors are used to control single and three-phase loads up to 63 A and can be operated by AC or DC.
These contactors are made for use in household applications as well as in industrial environments.
The following benefits are provided:
Hum-free operation, low power consumption and integrated overvoltage protection.
Various contact combinations and accessories are available.
Dimensions
- Product Net Width:54 mm
- Product Net Height:85 mm
- Product Net Depth / Length:65 mm
- Product Net Weight:0.385 kg
Technical
- Rated Operational Voltage:Main Circuit 220 V DC
Main Circuit 400 V AC - Rated Control Circuit Voltage (Uc):230 V
- Rated Frequency (f):Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Control Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
Main Circuit DC - Rated Operational Current AC-1 (Ie):(NO) 63 A
- Rated Operational Current AC-3 (Ie):(230 V) Single Phase, NO 30 A
(400 V) Three Phase, NO 30 A - Rated Operational Power AC-1 (Pe):(230 V) Single Phase, NO 14.5 kW
(400 V) Three Phase, NO 43.6 kW - Rated Operational Power AC-3 (Pe):(230 V) Single Phase, NO 5 kW
(400 V) Three Phase, NO 15 kW - Rated Operational Current AC-7a (Ie):(NO) 63 A
- Rated Operational Power AC-7a (Pe):(230 V) Single Phase, NO 14.5 kW
(400 V) Three Phase, NO 43.6 kW - Rated Operational Current AC-7b (Ie):(230 V) Single Phase, NO 30 A
(400 V) Three Phase, NO 30 A - Rated Operational Power AC-7b (Pe):(230 V) Single Phase, NO 5 kW
(400 V) Three Phase, NO 15 kW - Recommended Screw Driver:Control Circuit Pozidriv 1
Main Circuit Pozidriv 2 - Rated Impulse Withstand Voltage (Uimp):6 kV
- Rated Insulation Voltage (Ui):500 V
- Connecting Capacity Main Circuit:Flexible with Ferrule 1x 1.5 ... 16 mm²
Flexible with Ferrule 2x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 1x 1.5 ... 16 mm²
Flexible with Insulated Ferrule 2x 1.5 ... 10 mm²
Flexible 2x 1.5 ... 10 mm²
Flexible 1x 1.5 ... 16 mm²
Rigid 1x 1.5 ... 25 mm²
Rigid 2x 1.5 ... 10 mm² - Connecting Capacity Control Circuit:Flexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Ferrule 2x 0.75 ... 1.0 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1 mm²
Flexible 1x 1 ... 4.0 mm²
Flexible 2x 1 ... 2.5 mm²
Rigid 1x 1 ... 4 mm²
Rigid 2x 1 ... 2.5 mm² - Tightening Torque:Control Circuit 0.9 N·m
Main Circuit 2.5 N·m - Wire Stripping Length:Control Circuit 7 mm
Main Circuit 13 mm - Degree of Protection:IP20
- Electrical Durability:AC-1 (NO) 100000 cycle
AC-3 (NO) 240000 cycle
AC-7a (NO) 100000 cycle
AC-7b (NO) 240000 cycle - Mechanical Durability:1000000 cycle
- Number of Poles:3
- Number of Auxiliary Contacts NC:0
- Number of Auxiliary Contacts NO:0
- Number of Main Contacts NC:0
- Number of Main Contacts NO:3
- Width in Number of Modular Spacings:3
- Pollution Degree:3
- Standards:IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 61095
UL 60947-1
UL 60947-4-1
Technical UL/CSA
- Maximum Operating Voltage UL/CSA:Main Circuit 480 V AC
- Horsepower Rating UL/CSA:(220 ... 240 V AC) Single Phase, NO 5 Hp
(220 ... 240 V AC) Three Phase, NO 10 Hp
(440 ... 480 V AC) Single Phase, NO 7.5 Hp
(440 ... 480 V AC) Three Phase, NO 15 Hp - Connecting Capacity Main Circuit UL/CSA:Solid 16-4 AWG
Stranded 16-4 AWG - Connecting Capacity Control Circuit UL/CSA:Solid 16-10 AWG
Stranded 16-10 AWG - Tightening Torque UL/CSA:Control Circuit 8 in·lb
Main Circuit 20 in·lb
Environmental
- Ambient Air Temperature:Operation -25 ... +55 °C
Storage -40 ... +80 °C - Maximum Operating Altitude Permissible:2000 m
- Resistance to Shock acc. to IEC 60068-2-27:11 ms Pulse 15g
- RoHS Status:Following EU Directive 2011/65/EU